Surface-mounted temperature-humidity sensor with active and passive output



Application/Description
For the exact measurement of the relative humidity and temperature of air and other non-aggressive gases, the measured variable is converted into a standard signal. It is used as a surface-mounted sensor in refrigeration, air conditioning and clean room technology in living rooms, offices, hotels, etc. A digital, long-term stable sensor is used as a measuring element for humidity measurement. The temperature can be specified either actively or passively.
Technical Data
| Supply voltage: | 24 VAC ± 10% (only with voltage output) |
|---|---|
| Humidity working range: | 0...95% r.H. (without condensation) |
| Humidity accuracy: | ± 3% r.H. at 30...70% r.H., otherwise ± 5% r.H. |
| Temperature measuring range: | 0...+50°C |
| Temperature accuracy: | ±0.5K for U, ± 0.8 K for I |
| Output signal: | Humidity: 0 -10V or 4...20mA |
| Circuit type: | 2- or 3-wire connection |
| Ambient temperature: | Storage: -25...+60°C |
| Elec. connection: | using screw terminals 0.14...1.5mm² |
| Housing: | Plastic, color white (RAL 9010), optional stainless steel |
| Mounting: | Wall mounting or on flush-mounted box Ø=55mm |
| Protection class: | IP30 according to EN 60529 |
| Protection class: | III according to EN 60730 |